The PFS Fueltec Duty Standby Pump Control Panel is a modular microprocessor-controlled system designed for managing duty, standby, and assist operations in twin pumpsets. This panel is specifically engineered for transferring fuel from a bulk tank to a day tank, incorporating advanced features such as tank level controls, valve control, bund/seal leakage detection, and interfaces for BMS and fire systems. The innovative modular construction ensures flexibility and ease of customization, making it a reliable and efficient choice for various applications.
Typical Applications
- Duty/Standby/Assist Pumpsets: Compatible with pumpsets from any manufacturer.
- Diesel Fuel Transfer Sets: Extensively used with our diesel fuel transfer sets.
Optional Extras
- Additional Volt-Free Contacts: For external equipment integration.
- Internal RCDs: Interlocked with pump changeover, with an alarm for pump failure.
- Remote Dialler: For critical systems, sends text messages to your mobile phone.
- Run Time Counter: Monitors pump usage.
- Door Mount Ammeter: For easy current monitoring.
- Additional Interface Board: With the following functions:
- Day tank High High
- Day tank Low Low
- Bulk tank Low
- Bulk tank Low Low
- Pump 2 Fail (Overload or input from external flow switch)
- Emergency Stop
- Bund Alarm
- Fire Cut-off
- Pump 1 Fail (Overload or input from external flow switch)
- Flow switch
- Pump 1 run
- Pump 2 run
Please specify required outputs when ordering as a separate relay with volt-free contacts will be fitted for each required output.