Vacuum leak detector for the monitoring of a maximum of 12 tanks or pipes in a free-standing housing for outdoor installation.
The standard version is equipped with a green operating signal lamp, a red alarm signal lamp, an acoustic signal and its' acknowledgment button at the front panel as well as acknowledgment buttons for every interstitial space inside the housing (operation, alarm, pressure, pump run).
TYPES:
VLXE-SAB T34 for tanks with a suction line to the low point of the interstitial space
VLXE-SAB T330 for tanks with up to 3 meters diameter
VLXE-SAB P410 for filling and vapor recovery lines
VLXE-SAB P500 for suction lines
and the combined solutions
VLXE-SAB T34/P410
VLXE-SAB T34/P500
VLXE-SAB T330/P410
VLXE-SAB T330/P500
OPTIONAL EQUIPMENT:
Flashlight
LE: remote monitoring LOD with Ethernet module
TANKS/PIPES:
Tanks with a maximum internal overlay pressure of 500 mbar
Pipes with a maximum feed pressure in the inner pipe of 3.5 bar
STORED/CONVEYED PRODUCTS:
Water-polluting liquids. The (possible) explosive vapor-air mixtures (also such ones that can arise through the stored/conveyed liquids in contact with air, humidity, condensation or the materials used) must be classifiable into gas group II A to II B as well as in the temperature code T1 to T4. Examples: petrol, diesel, AdBlue.
INSTALLATION:
Outside the Ex area or in areas in which zone 1 does not exceed a height of 1 meter
HOUSING / TEMPERATURE RANGE:
st-box: steel box painted / unheated: -20 °C .. +60 °C, heated: -40 °C .. +60 °C
ss-box: stainless steel box / unheated: -20 °C .. +60 °C, heated: -40 °C .. +60 °C
PNEUMATIC CONNECTIONS:
QU8/6: quick union for polyamide (PA) hose 8/6x1mm.
(can be changed to CF8/6: compression ferrule for copper (CU) pipe 8/6x1mm by odering for each outlet article no. 425207-M)