12 input 2-wire sensor module. The EVO™ 550 and EVO™ 5000 Automatic Tank Gauges come standard with a power supply module and a controller module. Additional interface modules can be installed. Interface modules ordered with an ATG will be installed at the factory. The following guidelines must be followed:
EVO™ 550: Six total modules can be installed with a maximum of four intrinsically safe modules and a maximum of three of any one kind of module.
EVO™ 5000: Eleven total modules can be installed with a maximum of nine intrinsically safe modules and a maximum of three of any one kind of module.
TS-2WSNS 12 input 2-wire sensor module, TSP-ULS, TSP-UHS, TSP-HLS, and FMP-HFS sensors
The 2-Wire Sensor Module (2WSNS) is designed to accept 12
sensor inputs per module, and the system as a whole can accept
a total of 36 sensors (3 modules with 12 inputs each). The 2WSNS
only supports standard sensors, and does not accept inputs from
BriteSensors. Refer to the diagram below to identify some of the
standard sensors that can be used with this module
2-Wire Sensor Module
Number of Channels: 12
Safety Rating: Class I, Division 1, Group D, [Ex ia] IIA
Entity Parameters
Uo = 6.51 V
Io = 2.04 mA
Co = 500 uF
Lo = 100 mH
Po = 3.3 mW