8 input 4-20 mA module for ELLD and SCM. The EVO™ 550 and EVO™ 5000 Automatic Tank Gauges come standard with a power supply module and a controller module. Additional interface modules can be installed. Interface modules ordered with an ATG will be installed at the factory. The following guidelines must be followed:
EVO™ 550: Six total modules can be installed with a maximum of four intrinsically safe modules and a maximum of three of any one kind of module.
EVO™ 5000: Eleven total modules can be installed with a maximum of nine intrinsically safe modules and a maximum of three of any one kind of module.
TS-420IB 8 input 4-20 mA module, LSU500 transducers and VPS and SCCM pressure sensors
The Analog Input Module has 8 identical channels for loop powered
IS sensors with a 4-20 mA interface. The TS-550/5000evo
series can support up to 24 inputs (3 modules with 8 inputs
each) depending on available space in your console. The Analog
Input Module will most likely be used with: line leak pressure
transducers, tank pressure sensors and vacuum sensors.
Analog Input Module Specifications
Number of Channels: 8
Safety Rating: Class I, Division 1, Group D, [Ex ia] IIA
Entity Parameters
Uo = 26.25 V
Io = 98.2 mA
Co = 1.25 uF
Lo = 14.7 mH
Po = 0.64 W